If you found this page, you probably have a problem and you need a user manual for the device Burnham Hydronics MMII. Be sure to check that it is the user manual to exactly the device that you are looking for. In our database Burnham Hydronics MMII it belongs to the category Water Heater. A user manualBurnham Hydronics MMII is taken from the manufacturer, a Burnham company - it is an official document, so if you have any doubts as to its contents, please contact the manufacturer of the device Burnham Hydronics MMII directly. You can view the user manualBurnham Hydronics MMII directly online or save and store it on your computer.

I. Pre-Installation  
WARNING  
B. Appliance is design certied for installation on  
combustible ooring. The boiler must not be installed  
on carpeting.  
Carefully read all instructions before  
installing boiler. Failure to follow all  
instructions in proper order can cause  
personal injury or death.  
C. Provide clearance between boiler jacket and  
combustible material in accordance with local re  
ordinance. Refer to Figure 2 for minimum listed  
clearance from combustible material. Recommended  
service clearance is 24 inches from left side, right side,  
front and rear. Service clearances may be reduced to  
minimum clearances to combustible materials.  
A. Installation must conform to the requirements of the  
authority having jurisdiction. In the absence of such  
requirements, installation must conform to:  
USA  
ANSI Z223.1, National Fuel Gas Code.  
Where required by the authority having  
jurisdiction, the installation must also conform to  
ANSI/ASME CSD-1 Standard for Controls and  
Safety Devices for Automatically Fired Boilers.  
D. Install on leveloor. For basement installation provide  
concrete base if oor is not perfectly level or if water  
may be encountered on oor around boiler.  
E. Protect gas ignition system components from water  
(dripping, spraying, rain, etc.) during boiler operation  
and service (circulator replacement, condensate trap,  
control replacement, etc.).  
CANADA CAN/CGA B149.1 or .2 Installation Codes  
for Gas Burning Appliances and Equipment,  
and CSA C22.1 Canadian Electrical Code,  
Part I.  
Figure 2: Minimum Clearances to Combustible Surfaces  
4

In addition to the user manual Burnham Hydronics MMII, we also provide a support panel to help you solve your problems with Burnham Hydronics MMII. If you have any questions, you can ask them in the form below. Other users viewing this website will have the opportunity to help you solve your probem with Burnham Hydronics MMII. Remember that you can also share the solution. If you solved the problem yourself, please write the solution to the problem with Burnham Hydronics MMII - you will surely help many users by doing so.