Si has encontrado esta página, seguramente tienes un problema y necesitas el manual de instrucciones para el dispositivo Dialogic SS7G22. Recuerda comprobar si es el manual exacto para el dispositivo que buscas. En nuestra base Dialogic SS7G22 pertenece a la categoría Servidor. El manual Dialogic SS7G22 es del fabricante, la empresa Dialogic - es un documento oficial y si tienes alguna duda acerca de su contenido, contacta directamente con el fabricante del dispositivo Dialogic SS7G22. El manual Dialogic SS7G22 se puede ver directamente online o guardar y almacenar en tu ordenador.

Dialogic® SS7G21 and SS7G22 Signaling Servers Hardware Manual Issue 7  
WARNING  
IF DC POWER SUPPLIES ARE INSTALLED:  
ISOLATION:  
The product with DC input is to be installed in a Restricted Access Location in  
accordance with articles 110-16, 110-17 and 110-18 of the National Electric Code,  
ANSI/NFPA 70. The DC source must be electrically isolated by double or reinforced  
insulation from any hazardous AC or DC source. The DC source must be capable of  
providing up to 200 W of continuous power per feed pair. Connection to a DC source  
should only be performed by a QUALIFIED SERVICE TECHNICIAN.  
MAIN DC POWER DISCONNECT:  
You are responsible for installing a properly rated DC power disconnect for the entire  
rack unit. This DC power disconnect must be readily accessible, and it must be labelled  
as controlling power to the entire rack unit, not just to this product.  
GROUNDING THE RACK INSTALLATION:  
To avoid the potential for an electrical shock hazard, you must reliably connect a safety  
ground conductor to the product. The safety ground conductor must be a minimum  
1
4AWG connected to the safety ground studs on the rear of the product, with a closed  
two-hole crimp terminal. The nuts on the safety ground stud should be installed with a  
0 in/lbs torque. The safety ground conductor provides proper grounding only for this  
1
product. You must provide additional, proper grounding for the rack and other devices  
installed in it.  
OVERCURRENT PROTECTION:  
Overcurrent protection circuit breakers must be provided as part of each host  
equipment rack and must be installed between the DC source and this product. The  
branch circuit protection shall be rated minimum 75 VDC, 10 Amps maximum per feed  
pair. If the DC power system for the equipment rack is installed with more than 10  
Amps of protection, you must provide supplemental protection for this product. The  
overall current rating of this product configured with two power supplies is less than  
4
Amps.  
9

Además del manual Dialogic SS7G22 facilitamos un panel de soporte que te ayudará a solucionar tus problemas con Dialogic SS7G22. Si tienes alguna pregunta, puedes escribirla en el formulario más abajo. Otros usuarios que entran aquí tendrán la oportunidad de ayudarte en la solución de tu problema con Dialogic SS7G22. Recuerda que también puedes compartir tu solución. Si has logrado solucionar el problema, por favor escribe aquí la descripción y la solución del problema con Dialogic SS7G22 - seguro que ayudarás a muchos usuarios.