If you found this page, you probably have a problem and you need a user manual for the device Allied Telesis Switch X900-24XS. Be sure to check that it is the user manual to exactly the device that you are looking for. In our database Allied Telesis Switch X900-24XS it belongs to the category Switch. A user manualAllied Telesis Switch X900-24XS is taken from the manufacturer, a Allied Telesis company - it is an official document, so if you have any doubts as to its contents, please contact the manufacturer of the device Allied Telesis Switch X900-24XS directly. You can view the user manualAllied Telesis Switch X900-24XS directly online or save and store it on your computer.

Installation and Safety Guide  
Warning When SBx908 devices are connected with VCS stacking cables (either  
HS-STK-CBL or XEM-STK-CBL), each individual stack member chassis must be  
additionally grounded by using the rear grounding-terminal on each device. In  
order to avoid large circulating ground currents, the wires of each grounding  
cable must be 18AWG or thicker.  
PWR01 PWR01 DC  
DC  
Power supply specifications:  
functional range 40 to 60V, 48V nominal  
supports either positive grounded or negative grounded operation  
a 15Amp certified/listed circuit breaker is required for circuit protection  
Supply cable specifications:  
tray cable should be UL listed Type TC tray cable (or equivalent)  
three-core cable is required  
minimum core size: 3.3mm2 (12 AWG) high strand count copper wire  
minimum cable rating: 600V, 90 degrees C  
Warning Disconnect the power supply cable before starting this procedure.  
1
2
. Remove the transparent protective terminal cover.  
. Strip the supply cable wires to expose 7.5mm (0.31in.) of bare conductor.  
Terminate the wire with a nylon insulated solderless ring tongue terminal,  
JST FN5.5-5 or equivalent, using a crimp tool.  
3
4
. Connect the ground wire to the ground terminal. Use the diagram on the  
rear panel of the switch to identify terminals. Tighten the terminal to  
between 2.4 and 4.0 Nm (21.3 and 35.4 lbf in).  
. Connect the positive feed to the + (positive) terminal and the negative feed  
to the - (negative) terminal. Tighten the terminals to between 2.4 and  
4
.0Nm (21.3 and 35.4 lbf in).  
Note that the DC return input terminal must be connected as an Isolated  
DC return (DC-I).  
5
6
. Ensure that there are no exposed cable strands.  
. Replace the cover. You must replace the transparent plastic terminal cover  
before continuing.  
7
. Secure the supply cable to the rack framework or a similar object to ensure  
that connections are isolated from any force applied to the cable.  
1
3

In addition to the user manual Allied Telesis Switch X900-24XS, we also provide a support panel to help you solve your problems with Allied Telesis Switch X900-24XS. If you have any questions, you can ask them in the form below. Other users viewing this website will have the opportunity to help you solve your probem with Allied Telesis Switch X900-24XS. Remember that you can also share the solution. If you solved the problem yourself, please write the solution to the problem with Allied Telesis Switch X900-24XS - you will surely help many users by doing so.