Si has encontrado esta página, seguramente tienes un problema y necesitas el manual de instrucciones para el dispositivo Allied Telesis Switch X900-24XS. Recuerda comprobar si es el manual exacto para el dispositivo que buscas. En nuestra base Allied Telesis Switch X900-24XS pertenece a la categoría Interruptor. El manual Allied Telesis Switch X900-24XS es del fabricante, la empresa Allied Telesis - es un documento oficial y si tienes alguna duda acerca de su contenido, contacta directamente con el fabricante del dispositivo Allied Telesis Switch X900-24XS. El manual Allied Telesis Switch X900-24XS se puede ver directamente online o guardar y almacenar en tu ordenador.

Installation and Safety Guide  
Warning When SBx908 devices are connected with VCS stacking cables (either  
HS-STK-CBL or XEM-STK-CBL), each individual stack member chassis must be  
additionally grounded by using the rear grounding-terminal on each device. In  
order to avoid large circulating ground currents, the wires of each grounding  
cable must be 18AWG or thicker.  
PWR01 PWR01 DC  
DC  
Power supply specifications:  
functional range 40 to 60V, 48V nominal  
supports either positive grounded or negative grounded operation  
a 15Amp certified/listed circuit breaker is required for circuit protection  
Supply cable specifications:  
tray cable should be UL listed Type TC tray cable (or equivalent)  
three-core cable is required  
minimum core size: 3.3mm2 (12 AWG) high strand count copper wire  
minimum cable rating: 600V, 90 degrees C  
Warning Disconnect the power supply cable before starting this procedure.  
1
2
. Remove the transparent protective terminal cover.  
. Strip the supply cable wires to expose 7.5mm (0.31in.) of bare conductor.  
Terminate the wire with a nylon insulated solderless ring tongue terminal,  
JST FN5.5-5 or equivalent, using a crimp tool.  
3
4
. Connect the ground wire to the ground terminal. Use the diagram on the  
rear panel of the switch to identify terminals. Tighten the terminal to  
between 2.4 and 4.0 Nm (21.3 and 35.4 lbf in).  
. Connect the positive feed to the + (positive) terminal and the negative feed  
to the - (negative) terminal. Tighten the terminals to between 2.4 and  
4
.0Nm (21.3 and 35.4 lbf in).  
Note that the DC return input terminal must be connected as an Isolated  
DC return (DC-I).  
5
6
. Ensure that there are no exposed cable strands.  
. Replace the cover. You must replace the transparent plastic terminal cover  
before continuing.  
7
. Secure the supply cable to the rack framework or a similar object to ensure  
that connections are isolated from any force applied to the cable.  
1
3

Además del manual Allied Telesis Switch X900-24XS facilitamos un panel de soporte que te ayudará a solucionar tus problemas con Allied Telesis Switch X900-24XS. Si tienes alguna pregunta, puedes escribirla en el formulario más abajo. Otros usuarios que entran aquí tendrán la oportunidad de ayudarte en la solución de tu problema con Allied Telesis Switch X900-24XS. Recuerda que también puedes compartir tu solución. Si has logrado solucionar el problema, por favor escribe aquí la descripción y la solución del problema con Allied Telesis Switch X900-24XS - seguro que ayudarás a muchos usuarios.